10
2025
-
01
The container-level thermal runaway test conducted by AnDun has been successfully completed.
Author:
Ji Andun Fire Protection Technology
To meet the growing demand from customers for validation of container‑grade fire‑suppression system performance, Hubei Jian’an Dun Fire Technology Co., Ltd. conducted large‑scale thermal runaway tests on container‑grade systems from November 26 to 28, 2024. During the experiments, a complete alarm system, an exhaust ventilation system, and a 315 Ah battery pack were installed inside a standard 20‑foot container, and… Refer to domestic and international standards such as GB/T 36276, UL 9540A, and DB32/T 4682-2024. , overcharge and heating are used to simulate thermal runaway of the battery cell.
The experiment was conducted three times, employing different experimental protocols to evaluate the response times of smoke detectors, heat detectors, and combustible gas detectors following battery thermal runaway; the operational performance of the fire‑control system; whether aerosol discharge can ignite flammable gases within the container’s interior; and the fire‑extinguishing and suppression effectiveness of the aerosol fire‑suppression system at both the container level and the pack level.
01
Test model
Container (Length: 6.1 m, Width: 2.44 m, Height: 2.6 m)
Target pack (far right, bottom position, worst-case principle)
Target cell (at the far end, under the most unfavorable condition)
Cabin-level fire suppression system
probe
Pack-class fire-extinguishing system
Experimental Protocol
Experiment One
Arrange the test setup for fire‑extinguishing devices, detectors, electromagnetic igniters, and other components in accordance with the model’s installation requirements; ensure that the target pack remains unperforated. Then subject the target cell to overcharging: disconnect the charging equipment when the charging voltage reaches 0 V or when the temperature of the target cell’s large surface reaches 130°C and the rate of temperature rise remains ≥ 3°C/s for a continuous period of 3 seconds. Observe and record the response time and status of the fire‑suppression system. If the fire‑extinguishing device activates automatically, after the discharge is complete, use the electromagnetic igniter to initiate ignition (once every three minutes, for a total of ten consecutive ignitions).
Conclusion
Following thermal runaway of the battery, the container‑level fire suppression system was activated, initiating a discharge every three minutes for a total of ten consecutive discharges, with no re‑ignition observed. This demonstrates that the five AnDun QRR0.75G‑U01 aerosol fire suppression units can effectively suppress flammable gases within a 20‑foot container.
Following thermal runaway of the battery, the combustible gas detector responds promptly, followed closely by the smoke detector, with the heat detector providing the final response. This confirms that the fire‑control logic of the fire‑protection system provided by Proof and AnDun is functioning properly.
Following thermal runaway of the battery, five aerosol fire‑extinguishing units—both automatic and manual—were activated, along with the Andun QRR0.75G‑U01 aerosol fire‑extinguishing system. During discharge, the aerosol system failed to ignite the flammable gases inside the container, demonstrating that, in an environment containing flammable gases, the aerosol fire‑extinguishing system does not ignite the ambient flammable atmosphere.
Experiment Two
Arrange the experimental setup for aerosols, detectors, ignition devices, and other components in accordance with the model’s layout requirements. Create an opening on the top of the target pack, with an area equal to 5% of the upper‑cover surface, and extend this opening along the long side of the battery box. Then, activate the heating plate to heat the thermally runaway target cell, simultaneously turn on the video recording equipment, record the test start time and temperature, and monitor the process in real time. When significant flammable gas is detected at the explosion‑proof vent of the target box, or when the surface temperature of the target cell reaches 130°C and the rate of temperature rise remains ≥ 3°C/s for three consecutive seconds, disconnect the heating system and initiate remote ignition until open flame appears. Upon the appearance of open flame, manually activate the fire‑extinguishing system and observe its extinguishing performance.
Conclusion
After thermal runaway of the battery and ignition leading to open flames, activation of five AnDun QRR0.75G-U01 aerosol fire suppression units effectively extinguished the open flames within the container compartment. This demonstrates that five AnDun QRR0.75G-U01 aerosol fire suppression units can effectively suppress a compartment‑level fire in a 20-foot container.
Following thermal runaway of the battery, the combustible gas detector responds promptly, followed by the smoke detector, with the heat detector providing the final response. This confirms that the fire‑control logic of the fire‑protection system provided by Proof and AnDun is functioning properly.
Experiment Three
Arrange the test setup for the aerosol fire‑extinguishing system, detectors, ignition devices, and other components in accordance with the model’s installation requirements; drill an opening at the venting valve of the target pack. Activate the heating plate to heat the thermally runaway target cell, simultaneously turn on the video recording equipment, record the test start time and temperature, and monitor the process in real time. When significant flammable gas is detected at the explosion‑proof vent of the target enclosure, or when the surface temperature of the target cell reaches 130°C and the rate of temperature rise remains ≥ 3°C/s for 3 consecutive seconds, disconnect the heating equipment and initiate remote ignition until an open flame appears. Upon the appearance of an open flame, automatically activate the fire‑extinguishing system and observe its extinguishing performance.
Conclusion
Following thermal runaway of the battery and ignition until open flames appeared, the QRR 0.144 G/s aerosol fire suppression system automatically activated, successfully extinguishing the open flames within the battery pack. This demonstrates that a single AnDun QRR 0.144 G/s aerosol fire suppression unit can effectively suppress fires at the 315 Ah pack level.
Following thermal runaway of the battery, the combustible gas detector responds promptly, followed by the smoke detector, with the heat detector providing the final response. This confirms that the fire‑control logic of the fire‑protection system provided by Proof and AnDun is functioning properly.