The failure of lithium batteries in electrochemical energy storage systems is primarily attributed to thermal runaway, and the risk of thermal runaway increases as the batteries age. Moreover, once a cell experiences thermal runaway, the process is irreversible; therefore, controlling the propagation of thermal runaway at its source is of paramount importance. An increasing number of energy‑storage manufacturers are attempting to mitigate this by monitoring various battery parameters and implementing corrective measures. However, if these measures fail, they can give rise to additional secondary risks, potentially triggering further thermal runaways. Consequently, TRPP system Become the optimal backup solution for critical safety systems.
1
Background and Concept
TRPP stands for Thermal Runaway Propagation Prevention and is designed to provide an effective system for preventing the propagation of thermal runaway.
As early as the initial stages of the production and application of electrochemical energy storage systems, China, by investigating the root causes of safety incidents, issued in 2022… GB/T 42288 In the “Safety Code for Electrochemical Energy Storage Power Stations,” an automatic fire‑extinguishing system is incorporated into the smallest protective unit—the lithium‑ion battery module—to suppress fires and prevent reignition, aligning with the TRPP concept outlined in the U.S. NFPA 855, which is currently undergoing revision.
2
Test status
01
Thermal Runaway Fire Spread Test (UL 9540A)

1 When thermal runaway occurs within a battery module without open flames,
Battery casing reaches 252.4 °C Thermal runaway occurs; after thermal runaway ends, the maximum temperature inside the module is… 84.6 °C , no thermal runaway occurred.
2
When thermal runaway and open flames occur within the battery module,
53 point 11 A flame appears in seconds, 10 Within seconds TRPP Initiate extinguishing operations Only the battery cell being heated and the two adjacent cells experience thermal runaway, with no other thermal propagation.
02
Large-scale fire test ( UL 9540B & CSA C800 )
Given that batteries used in energy storage systems may experience thermal runaway without visible flames, the AHJ requires testing of these batteries beyond the scope of UL 9540A. This is done to meet the large-scale fire‑testing requirements stipulated in various codes, such as the California Fire Code and the International Fire Code. According to these codes, the purpose of this test is to… Let a single The ESS device is fully engulfed in flames. , to determine whether the fire will spread to adjacent areas ESS equipment.
The Commentary on the International Firefighting Law further underscores this point, stating that… “Large-scale fire tests are essential for demonstrating that flame spread from unit to unit does not occur and for generating additional data needed to conduct risk assessments for different installation locations.”
The 2026 edition of NFPA 855 will include the large-scale fire‑testing standard in Appendix G, under the Guidelines for Suppression and Safety of Lithium‑Ion Battery (LIB) Energy Storage Systems (ESS).
3
TRPP Preliminary Requirements
(Expected) 2025 Released at the end of the year NFPA 2026 Version)
As a critical safety component in UL 9540 Certification Internally assessed
The discharge of the extinguishing agent is controlled by a fire alarm control unit that has been certified for release.
Refer to section 4.10 to ensure power supply requirements are met.
According to the corresponding NFPA Standard Perform debugging and record according to Section 9.6.4.
Inspect and test at least annually.
Space and area protection for energy storage systems that cannot be replaced
Conduct specialized tests tailored to the specific application to assess its reliability and survivability.