Interpretation of North American NFPA Fire Safety Regulations for Energy Storage (Part 3) — New Requirements for Explosion Control System Design
Author:
The 2026 edition of NFPA 855 imposes more stringent requirements on the design of explosion control systems. May involve changes to the references to NFPA 68 and NFPA 69. , as well as adjustments to the backup power duration.
The following provides a detailed analysis of the relevant changes:
NFPA 68 is a standard published by the National Fire Protection Association, officially titled “Standard on Venting and Suppression Systems for Deflagrations.” This standard specifies requirements for the installation and operation of equipment and systems designed to vent combustion gases and pressure generated by deflagrations within containment enclosures, with the aim of minimizing damage to structures and machinery. NFPA 68 is regarded as a passive protection strategy that mitigates the effects of explosions by relieving pressure inside the system and venting combustion gases in a safe direction.
NFPA 69, officially titled “Standard on Explosion Protection Systems,” specifies requirements for the design, installation, operation, maintenance, and testing of systems intended to prevent or control deflagrations and explosions. It addresses explosion prevention through methods such as controlling oxidizer concentrations, managing flammable vapor concentrations, implementing explosion suppression, regulating deflagration pressures, and employing spark‑extinguishing systems.
NFPA 855 has undergone numerous significant revisions. Notably, the first major change is that NFPA 68 is no longer permitted as a standalone explosion‑control method; it may only be used in conjunction with an NFPA 69 explosion‑control system. The NFPA 69 system is typically an active ventilation system triggered by gas detectors, whose primary function is to remove flammable gases from the protected area. The standards committee made this decision because explosion prevention is the top priority in hazard mitigation, and ventilation—being the most widely accepted approach for achieving this goal—should be given precedence.
Another related change is that, if an NFPA 69 system is provided, a partial‑volume deflagration analysis will be required. This may result in certain BESS enclosures incorporating both NFPA 69 and NFPA 68 systems. Furthermore, the use of other custom‑designed engineering systems will remain permitted, provided that fire‑protection testing has been conducted in advance and the system’s performance has been verified.

In the 2023 edition of NFPA 855, for energy storage systems located within rooms or buildings, as well as for systems such as battery cabinets and walk-in energy storage units, explosion‑control requirements may be satisfied by either NFPA 68 or NFPA 69, thereby providing a degree of flexibility in the design and implementation of these systems.

Meanwhile, the 2026 edition of NFPA 855 introduces even stricter requirements: all ESSs must be equipped with a reliable explosion control and prevention system, whose design, installation, operation, maintenance, and testing shall comply with NFPA 69. In addition, a partial‑volume deflagration assessment must be conducted in accordance with NFPA 68 to further enhance the safety and reliability of energy storage systems.
In essence, the requirements for backup power are determined by combining HMA data with UL 9540A test results and assumptions incorporating a safety factor. Although a 24-hour backup power supply is still recommended, the duration under alarm conditions may vary depending on 9540A data, container design, and other factors, and must be assessed and finalized on a case-by-case basis.

The 2023 edition of NFPA 855 specifies the following backup power requirements for gas detection systems: For lithium-ion batteries, the system shall provide at least 24 hours of standby power and 2 hours of alarm‑triggering power, or comply with the requirements of the HMA.

The 2026 edition of NFPA 855 requires that backup power sources be determined using HMA data in conjunction with UL 9540A data and assumptions based on safety factors. It may also mandate a 24-hour backup power supply, though the duration under alarm conditions could vary depending on the 9540A data, the energy storage system design, and other variables.
Current standards require gas detection and explosion‑control systems to be equipped with a 24‑hour standby power supply and a 2‑hour alarm‑support power supply. However, in certain situations, this may not be sufficient. Accordingly, the committee has determined that the duration of battery backup should be established through a so‑called Hazard Mitigation Analysis (HMA) prepared by a qualified design professional. NFPA 855 will reference NFPA 110 for emergency and standby power systems and mandates that batteries meet either Type 10 or Class 2 requirements. Type 10 systems must transfer power within 10 seconds, while Class 2 is a classification for systems that are less critical to life safety. Crucially, the length of standby power will no longer be prescribed; instead, it will be determined on a case‑by‑case basis by the facility’s records or by a licensed design engineer.