AHJ Dialogue: Insights into Compliance for Energy Storage Exports in 2025 (Part I)
Author:
In 2025, the global energy storage market is set to experience significant growth, and the associated fire safety challenges are increasingly coming to the fore. In response to fire safety and related system issues in overseas energy storage projects, our company has engaged specialized overseas consultants. AHJ, which collaborates closely with AnDun, has obtained abundant and valuable information.
This article will provide a brief analysis of market trends in the energy storage sectors of Europe and North America through 2025, aiming to spark further discussion. Furthermore, AnDun will extensively gather insights on key industry topics such as trends in energy storage development, policy impacts, and market prospects, while proactively engaging in regular exchanges with expert advisors from Europe, North America, and Australia. By providing cutting-edge, authoritative analysis, we aim to support Chinese energy‑storage clients as they expand into international markets.
Does installing a TRPP inside the battery pack require certification?
As TRPP is a newly introduced feature, no relevant certification standards are currently available. The comparative test results conducted in conjunction with CSA may be submitted as part of the UL 9540 certification, while an engineering assessment report prepared by a third-party professional fire‑safety engineer can serve as supplementary documentation to validate the reliability and effectiveness of this solution.
What are the requirements for TRPP media?
Currently, the solutions known in the United States include perfluorohexanone and Fike Blue; however, because they require a release‑triggering signal, they must be paired with a host unit certified for activation and an auxiliary power supply. In contrast, AnDun’s TRPP eliminates the need for a host unit and backup power source and requires no maintenance.
Specific details regarding the backup batteries mentioned in the NFPA 855 revision How do I configure it?
Currently, the explosion‑control system—comprising combustible‑gas detection and smoke‑exhaust fans—requires a backup power supply to operate continuously for 24 hours and to sustain an alarm condition for 2 hours. Starting with the next version, the duration of the backup power will be verified by a professional fire‑protection engineer in accordance with HMA, and, based on the overall BESS configuration, larger‑capacity backup batteries may be employed.
Will UL 9540A require flammable gases to be ignited? Add an ignition test to
Identifying the hazards of energy storage systems?
The NFPA 855 committee has proposed adding an ignition test to UL 9540A to assess flame spread and verify clearance distances under real‑world installation conditions. 。
Does a combustible gas detector need to comply with UL 2075? And FM-related certifications?
UL 2075 and FM certification are not required. Some AHJs may impose such requirements locally. Not all gas sensors are UL 2075– or FM‑certified. Upon further consideration, ATEX certification is also not mandatory, though some AHJs may still require it. ESS cannot perform electrical classification; therefore, gas sensors do not need to be electrically classified. According to the International Mechanical Code, fans must be spark‑proof. 。
Will large-scale fire‑testing be mandated?
This has always been the original intent of the NFPA 855 committee, and many external stakeholders are now calling for mandatory large‑scale fire‑testing to ensure there are no adverse environmental impacts. However, the timing of such mandatory requirements will depend on whether the new edition of NFPA 855 is adopted at the project’s location. The publication of a standard does not mean it will be immediately embraced everywhere; some states may not adopt this version until as late as 2030. To our knowledge, one jurisdiction has already mandated it.
When calculating the aerosol dosage, is it necessary to subtract…? What are the dimensions of the battery rack and the battery module?
Determine the protected space according to the corresponding aerosol product manual. Generally, battery racks and battery modules, even with high IP ratings, are penetrable; therefore, their volume does not need to be subtracted. 。
What is the difference between UL 9540B and CSA C800?
UL 9540B applies exclusively to residential energy storage systems (under 20 kWh) and is currently only a draft outline issued by UL, with no formal testing methods yet available. Meanwhile, CSA plans to release the first draft of its large‑scale fire‑testing standard, C800, around April next year, soliciting industry input and feedback before finalizing the document. 。
What are the basic requirements for deploying energy storage containers?
The maximum container height is 18 meters, and there is no upper limit on the energy storage capacity. To proceed with the project, the following documentation must be provided: UL 9540 certification, a UL 9540A test report, project engineering drawings, a hazard mitigation analysis, an emergency response plan, and a compliance assessment report issued by a third-party licensed fire protection engineer.
What are the certification requirements for water fire‑fighting components?
Section 7.1.1.2 of NFPA 13 requires that all water‑fire‑protection components (materials and devices) essential for system operation be certified. Water‑fire‑protection piping—steel pipe (welded or seamless) and copper pipe (drawn or seamless)—is exempt from certification if installed in accordance with the applicable standards, and components that do not affect system performance are also not required to be certified.