The container-level thermal runaway test conducted by AnDun has been successfully completed.

Author:



Quick Look at New Information

Let’s take a look at what big moves Yian Dun has in store.



To meet the growing demand from customers for validation of container‑grade fire‑suppression system performance, Hubei Jian’an Dun Fire Technology Co., Ltd. conducted large‑scale thermal runaway tests at the container level from November 26 to 28, 2024. During the experiment, a complete alarm system, an exhaust ventilation system, and a 315 Ah battery pack were installed inside a standard 20-foot container, and… Reference GB/T36276 , UL9540A, DB32/T 4682-2024 Domestic and international standards , overcharge and heating are used to simulate thermal runaway of the battery cell.

The experiment was conducted three times, using different experimental protocols to verify. The response times of smoke detectors, heat detectors, and combustible gas detectors following battery thermal runaway; the operational status of the fire‑control system; whether aerosol discharge can ignite flammable gases within the container’s interior space; and the fire‑extinguishing and suppression performance of aerosol fire‑suppression systems at both the container level and the pack level.





0 1
Test model

Container (Length: 6.1 m, Width: 2.44 m, Height: 2.6 m)



Target pack (far right, bottom position, worst-case principle)



Target cell (at the far end, under the most unfavorable condition)



Cabin-level fire suppression system



Probe



Pack-class fire suppression system




Experimental Protocol



Experiment One




Arrange the test setup for fire‑extinguishing devices, detectors, electromagnetic igniters, and other components in accordance with the model’s installation requirements; ensure that the target pack remains unperforated. Subsequently, subject the target cell to overcharging: disconnect the charging equipment when the charging voltage reaches 0 V or when the temperature of the target cell’s large surface exceeds 130°C and the rate of temperature rise remains ≥ 3°C/s for at least 3 consecutive seconds. Observe and record the response time and status of the fire‑suppression system. If the fire‑extinguishing device activates automatically, perform ignition using the electromagnetic igniter after the discharge is complete (ignition once every three minutes, repeated ten times consecutively).


Conclusion


  • Following thermal runaway of the battery, the container‑level fire suppression system was activated, initiating a discharge every three minutes for a total of ten consecutive discharges, with no re‑ignition observed. This demonstrates that the five AnDun QRR0.75G‑U01 aerosol fire suppression units can effectively suppress flammable gases within a 20‑foot container.

  • Following thermal runaway of the battery, the combustible gas detector responds promptly, followed by the smoke detector, with the heat detector providing the final response. This confirms that the fire‑control logic of the fire‑protection system provided by Proof and AnDun is functioning properly.

  • Following thermal runaway of the battery, five aerosol fire‑extinguishing units—both automatic and manual—were activated, along with the Andun QRR0.75G‑U01 aerosol fire‑extinguishing system. During discharge, the aerosol system failed to ignite the flammable gases inside the container, demonstrating that, in an environment containing flammable gases, the aerosol fire‑extinguishing system does not ignite the ambient flammable atmosphere.





Experiment Two




Arrange the aerosol, detectors, ignition devices, and other test equipment according to the model’s layout requirements. Drill an opening above the target pack, with an area equal to 5% of the top cover’s surface, along the long side of the battery box. Then activate the heating plate to heat the thermally runaway target cell, simultaneously turn on the video recording system and log the test start time and temperature, while monitoring in real time. If a large amount of flammable gas is detected at the explosion‑proof vent of the target enclosure, or if the surface temperature of the target cell reaches 130°C and the rate of temperature rise remains ≥ 3°C/s for three consecutive seconds, disconnect the heating equipment and initiate remote ignition until open flame appears. Once open flame is observed, manually activate the fire‑extinguishing system and assess its extinguishing performance.


Conclusion
  • After thermal runaway of the battery and ignition leading to open flames, activation of five AnDun QRR0.75G-U01 aerosol fire suppression units effectively extinguished the open flames within the container compartment. This demonstrates that five AnDun QRR0.75G-U01 aerosol fire suppression units can effectively suppress a compartment‑level fire in a 20-foot container.

  • Following thermal runaway of the battery, the combustible gas detector responds promptly, followed by the smoke detector, with the heat detector providing the final response. This confirms that the fire‑control logic of the fire‑protection system provided by Proof and AnDun is functioning properly.





Experiment Three




Arrange the test setup for the aerosol fire‑extinguishing system, detectors, ignition devices, and other components in accordance with the model’s installation requirements; drill a hole at the venting valve of the target pack. Activate the heating plate to heat the thermally runaway target cell, simultaneously turn on the video recording equipment, and record the test start time and test temperature while monitoring in real time. If substantial flammable gas is detected at the explosion‑proof vent of the target enclosure, or if the surface temperature of the target cell reaches 130°C and the rate of temperature rise remains ≥ 3°C/s for three consecutive seconds, disconnect the heating equipment and initiate remote ignition until an open flame appears. Upon the appearance of an open flame, automatically activate the fire‑extinguishing system and observe its extinguishing performance.


Conclusion
  • Following thermal runaway of the battery and ignition until open flames appeared, the QRR0.144G/S aerosol fire suppression system automatically activated, successfully extinguishing the open flames within the battery pack. This demonstrates that a single AnDun QRR0.144G/S aerosol fire suppression unit can effectively suppress fires at the 315 Ah pack level.

  • Following thermal runaway of the battery, the combustible gas detector responds promptly, followed by the smoke detector, with the heat detector providing the final response. This confirms that the fire‑control logic of the fire‑protection system provided by Proof and AnDun is functioning properly.




END