In-Depth Analysis and Compliance Guide for the 2026 Edition of NFPA 855 (Part II) — TRPP Systems, Automatic Fire Control, and Fire Suppression Systems

Author:



Introduction

The failure of lithium batteries in electrochemical energy storage systems is primarily attributed to thermal runaway. As batteries age, the risk of thermal runaway increases, and once a cell experiences thermal runaway, the process becomes irreversible. Therefore, addressing thermal runaway at its source is of paramount importance. TRPP systems and automated fire‑suppression and extinguishing systems have become critical components of safety infrastructure. The 2026 edition of NFPA 855 has been updated to reflect these requirements, which will be examined in detail below.


PART. 1


Preliminary Requirements for TRPP in the 2026 Edition of NFPA 855


1

Evaluated as a critical safety component under UL 9540 certification.

2

The discharge of the extinguishing agent is controlled by a fire alarm control unit that has been certified for release.

3

Refer to section 4.10 to ensure power supply requirements are met.

4

Commissioned in accordance with the applicable NFPA standards and documented as specified in Section 9.6.4.

5

Inspect and test at least annually.

6

Space and area protection for energy storage systems that cannot be replaced

7

Conduct specialized tests tailored to the specific application to assess its reliability and survivability.

Furthermore, Yian Dun’s overseas experts serve as members of the NFPA 855 Technical Committee, and our company is currently working to incorporate Yian Dun’s TRPP products into the aforementioned preliminary requirements.


Current System Research of TRPP



Application Cases and Validation Methods of the AnDun TRPP System



To verify product compliance and reliability, Ji’andun is also collaborating with UL to conduct third-party assessments and certification testing of TRPP products’ system performance.


PART.2

Updated Description of Automatic Fire Control and Extinguishing Systems

 2023 Edition Original Text 1.png  2023 Edition Original Text 2.png

In Chapter 4.9 of the 2023 edition, NFPA 13 automatic sprinkler systems are designated as the default installed system, while the remaining six categories of systems (NFPA 12, NFPA 15, NFPA 750, NFPA 770, NFPA 2001, and NFPA 2010) are listed as alternative automatic fire suppression systems. 。


 2026 version original text.png

In the 2026 edition, the description of alternative terms has been removed, and NFPA 13 along with the other six categories of automatic fire‑suppression and fire‑control systems are now regarded as equivalent standards. This means that, when selecting a fire‑suppression system, BESS manufacturers need only install a fixed aerosol fire‑extinguishing system compliant with NFPA 2010 to meet regulatory requirements.


NFPA 13 – Standard for the Installation of Sprinkler Systems
(Standard for the Installation of Automatic Sprinkler Systems)

NFPA 12 – Standard on Carbon Dioxide Extinguishing Systems

(Carbon Dioxide Fire-Extinguishing System Standard)

NFPA 15 – Standard for Water Spray Fixed Systems for Fire Protection
(Standard for Fixed Water Spray Fire-Extinguishing Systems)

NFPA 750 – Standard on Water Mist Fire Protection Systems
(Standard for Water Mist Fire Suppression Systems)

NFPA 770 – Standard on Hybrid (Water and Inert Gas) Fire-Extinguishing Systems
(Standard for Hybrid Fire Suppression Systems – Water + Inert Gas)

NFPA 2001 – Standard on Clean Agent Fire Extinguishing Systems
(Standard for Clean Gas Fire Suppression Systems)

NFPA 2010 – Standard for Fixed Aerosol Fire-Extinguishing Systems
(Standard for Fixed Aerosol Fire-Extinguishing Systems)