In-Depth Analysis and Compliance Guide to the 2026 Edition of NFPA 855 (Part I) — A Clause-by-Clause Examination of Key Updates to Energy Storage Fire Safety Provisions (Part I)
Author:
NFPA 855 is the standard code for the installation of stationary energy storage systems (ESS), establishing minimum installation requirements for residential, commercial, and grid‑scale energy storage systems. First published in 2019, the standard is updated every three years to address the rapidly evolving landscape of the energy storage sector.
The 2026 edition of NFPA 855 represents the third revision of this standard—following the 2020 and 2023 editions—and is expected to be officially published in the fall of 2025. The new edition will incorporate significant updates from previous versions, addressing emerging requirements related to energy storage technologies, flow‑battery systems and deployment strategies, thermal runaway propagation protection systems, explosion‑proof control systems, emergency response plans, backup power supply, as well as fire and explosion testing.
To help Industry peers and partners are taking the lead in grasping the key points of the new regulations, and AnDun Fire Protection has specially launched the “2026 Edition of NFPA.” “855 In-Depth Analysis and Compliance Guide” series. This series will draw on our company’s extensive expertise in energy storage fire safety, combined with insights from North American professional fire engineers, to deliver comprehensive guidance—from regulatory interpretation to practical technical implementation.
As the inaugural installment of this series, this issue focuses on the original text of regulations most closely related to fire safety, distilling and translating, clause by clause, the key updates to the 2026 edition of NFPA 855, so you can grasp the regulatory changes at a glance.
Translation:
4.2.1.1 Design documents and specifications related to the ESS, including its planned installation, replacement or upgrade, commissioning, and operation, shall be submitted for AHJ approval and shall include the following:
(1) Floor plans and location maps of the rooms or areas where the energy storage system is planned to be installed;
(2) A detailed description of the fire-resistance rating (in hours) of fire-resistant components that are related to or dependent on the energy storage system;
(3) The number and types of energy storage system units;
(4) List of manufacturer specifications, ratings, and certifications for the energy storage system;
(5) Description of the Energy Storage Management System (ESMS) and its operating mode;
(6) The location and content of required signage;
(7) Detailed descriptions of the installed fire suppression, smoke detection, fire detection, gas detection, thermal management, exhaust ventilation, as well as explosion-proof and protective systems;
(8) Support arrangements related to installation, including the required seismic supports.
Translation:
4.2.1.2 In accordance with the provisions of the North American Electric Reliability Corporation and other applicable government laws and regulations, plans and specifications pertaining to energy storage systems owned and operated by utility companies as part of the electric grid shall be deemed critical infrastructure documents and shall be made available to the AHJ for review in compliance with the requirements of applicable government laws and regulations.
4.2.1.3 In addition to the plans and specifications set forth in 4.2.1.1, the following test data, evaluation information, and calculations required by other sections of this standard shall also be provided:
(1) Fire and explosion test data provided in accordance with Section 9.2
(2) Hazard Mitigation Analysis (HMA) provided in accordance with Section 4.4
(3) Calculation or modeling data used to determine compliance with explosion control and prevention requirements, as specified in 9.7.6.7.3.
(4) Other test data, evaluation information, or calculations required by other sections of this standard.
4.2.1.4 If modeling data are provided, validation of the modeling results shall also be included.
Translation:
4.4 Hazard Mitigation Analysis (HMA)
4.4.1 Unless modifications have been made in Chapters 9 through 17, a hazard mitigation analysis report shall be submitted to the AHJ for review and approval.
4.4.2 Failure Modes
Hazard mitigation analysis shall assess the consequences of the following scenarios:
(1) Thermal runaway or mechanical failure of a single ESS unit
(2) Faults in energy storage management systems or protection systems that are not covered by the product’s Failure Mode and Effects Analysis (FMEA)
(3) Essential system failures, including but not limited to HVAC, liquid cooling systems, BMS, communication systems, or other critical systems that may affect normal operation.
(4) Other failure modes required by the AHJ

Translation:
4.4.2.2 For each mode specified in 4.4.2.1, only a single failure mode shall be considered.
4.4.2.3 The HMA shall assess the reliability and survivability of the following critical safety components or systems in the event of thermal runaway propagation or a single failure:
(1) Exhaust ventilation
(2) Smoke Detection
(3) Fire Detection
(4) Firefighting
(5) Combustible Concentration Reduction (CCR) System
(6) Gas Detection
(7) Explosion Control and Prevention
4.4.3 If the analysis results indicate any of the following conditions, the AHJ shall be authorized to approve the hazard mitigation analysis as evidence of the safety of the ESS installation:
(1) Within the minimum time specified for the fire-resistance rating in 9.7.5, the fire shall be contained within the unoccupied ESS compartment.
(2) The fire and its combustion products shall not impede the evacuation of occupants to a safe location.
(3) The risk of deflagration will be addressed by the explosion control and prevention system.
Translation:
4.8.1 In addition to the other requirements of this standard, unless modified in accordance with the provisions of Chapters 9 through 13, areas containing ESS shall be equipped, as specified by NFPA 72, with smoke detection, thermal‑imaging fire detection, or radiant‑energy sensing systems.
4.8.2 Alarm
4.8.2.1 All necessary alarm devices shall be installed in accordance with the requirements of the competent authorities to facilitate an effective response to the situation. [72:10.18.3.2]
4.8.2.2* Multiple panels shall be consolidated into a master panel or alarm panel at the fire command center or another approved location.
4.8.3 Alarm signals generated by the detection system shall be transmitted to the monitoring station in accordance with NFPA 72.
Translation:
4.9.4 Automatic Fire Control and Suppression Systems
4.9.4.1 Automatic fire detection and suppression systems shall comply with the following standards or their equivalents, unless otherwise specified in Chapters 9 through 17:
(1) NFPA 13
(2) NFPA 12
(3) NFPA 15
(4) NFPA 750
(5) NFPA 770
(6) NFPA 2001
(7) NFPA 2010
4.9.4.2. Reports based on the results of large-scale fire and explosion tests conducted in accordance with Section 9.2 permit the use of alternative automatic fire detection and suppression systems.
4.9.4.3. Fire control and suppression systems that are part of the Thermal Runaway Propagation Protection System (TRPP) shall comply with the requirements of 9.7.6.6.
Translation:
4.10 Emergency Power Supply System (EPSS)
Reliable EPSS or SEPSS power supplies must be provided for critical safety systems that rely on electrical power, in accordance with NFPA 110 or NFPA 111.
4.10.1 If EPSS or SEPSS is provided, it shall be Class X, Type 10, Level 2.
4.10.2 Energy Storage Design
4.10.2.1 Registered professional designers with an EPSS design background shall assess the duration and total load requirements and determine the specific loads of the power system.
4.10.2.2 The EPSS design shall be submitted to the registered fire protection engineer (FPE) and the AHJ for review and approval.
4.10.3 The Category 10 requirements of EPSS or SEPSS shall permit increases based on HMA assessments and the transfer of safety loads to critical infrastructure.
4.10.4 The installation of the EPSS shall comply with the requirements of Section 7.2 of NFPA 110 and provide isolation and protection to ensure that system operation is not affected in the event of a failure.
Translation:
7.1.2 The operation and maintenance documentation shall include the following:
(1) Procedures for starting up and shutting down the ESS and related equipment
(2) Inspection and testing procedures for related alarms, interlocks, and controls
(3) Maintenance and operating procedures for the following equipment (where applicable):
(a) Energy Storage Management System (ESMS)
(b) Firefighting Equipment and Systems
(c) Leakage Control and Neutralization System
(d) Exhaust and ventilation equipment and systems
(e) Gas detection system
(f) Other necessary safety equipment and systems
(4) Precautions for handling similar to those in the Safety Data Sheet (SDS), addressing safety concerns, and extinguishing fires when an SDS is not required.
(5)* Instructions regarding the requirement to document any changes to equipment or system installations by updating all relevant engineering documents.