In-Depth Analysis and Compliance Guide for the 2026 Edition of NFPA 855 (Part Four) — System Breakdown: Explosion‑Proof Fans and Recent Changes to CCR

Author:



Introduction

In the 2026 edition of NFPA 855, this series of in-depth analyses and compliance guides has, in its first three installments, reviewed the foundational provisions, conducted a thorough examination of the new requirements for TRPP systems and automatic control and fire suppression systems, and explained the rigorous scenarios of large-scale fire‑burn tests. The final installment of this series will focus on the most explicit and stringent configuration under NFPA 855—explosion‑proof control—exploring its technical requirements and design rationale.



As competition in the energy storage industry intensifies and new technologies continue to emerge, explosion‑proof control has become the most hotly debated topic at this edition’s Technical Committee meeting. In Chapter 9 of the 2023 edition, which addresses electrochemical energy storage systems, the requirements for explosion control are as follows:

9.6.5.6.3 ESS units installed in rooms, buildings, ESS cabinets, ESS walk-in units, or other enclosed spaces that cannot be occupied shall be equipped with one of the following systems:

(1) Explosion-proof systems designed, installed, operated, maintained, and tested in accordance with NFPA 69;

(2) Deflagration venting devices installed and maintained in accordance with NFPA 68.

Due to the limited internal space in some cabinet enclosures, the safety‑oriented design of engineered deflagration can be thoroughly validated using test data from UL 9540A at both the cell and system levels. NFPA 68 applies to the design, location selection, installation, maintenance, and operation of venting devices and systems intended to discharge combustion gases and pressures generated by deflagrations within enclosed spaces, with the goal of minimizing structural and mechanical damage and providing standards for the design, installation, and maintenance of deflagration vents and their associated components. However, NFPA 68 does not address explosions; the accumulation of hydrogen in confined spaces can lead to explosive conditions. Therefore, the combustion gases produced during testing of battery cells, modules, and system‑level assemblies according to UL 9540A must be used to implement NFPA 68–compliant venting solutions. If there is a potential for explosion, alternative solutions outlined in NFPA 69 should be considered.

Data on the composition and release rates of flammable gases—such as that generated in UL 9540A fire and explosion testing—provide the critical information needed to design effective explosion‑control systems. Consequently, many energy‑storage system integrators rely on top‑mounted venting panels as their primary means of explosion control.

 Image 1 from Series Article Four.png

However, the 2026 edition of NFPA 855 recognizes that, while NFPA 68 previously served as a standalone approach for explosion control and prevention, when NFPA 68 is used in lieu of NFPA 69 or when it is necessary to achieve an explosion‑proof design objective, performance‑based design shall be conducted in accordance with Section 9.6.6.6.5. This allows reducing the concentration of flammable gases to serve as an effective mitigation strategy for addressing the potential accumulation of flammable gases in lithium‑ion batteries under abnormal conditions. Consequently, the 2026 edition of NFPA 855 explicitly incorporates explosion control and prevention as a separate subsection.




Even though the NFPA 69 system cannot guarantee the prevention of deflagrations, it can significantly mitigate potential consequences by reducing the total quantity of flammable gases. Small quantities of gas exceeding the Lower Flammable Limit (LFL), particularly at the source of the release, may ignite and result in a partial-volume deflagration.

The 2026 edition of NFPA 855 states that, even when designed in accordance with NFPA 69 to ensure that the average volumetric concentration of gases within the relevant battery‑enclosure compartments does not exceed 25% of the lower flammable limit (LFL), pockets of gas concentrations above the LFL may still occur at the source of release and in stagnant zones. Consequently, a partial‑volume deflagration study under NFPA 68 is required, particularly for large‑capacity enclosures, where the average concentration of flammable gases must remain below 25% of the LFL. Moreover, measures to prevent the release of flammable gases during normal operation shall comply with the requirements for mechanical ventilation systems, thereby making NFPA 69 the primary means of explosion control and prevention. At the same time, compliance with NFPA 68 for partial‑volume deflagration assessments is mandated, which overturns the 2023 edition’s design approach of selecting one of the two systems. However, given the coexistence of both systems, the venting area required by NFPA 68 may be significantly reduced.

When conducting partial‑volume deflagration analyses, CFD modeling is essential. After evaluating factors such as the layout of equipment within the energy storage system, air intake openings, overall gas movement, detector placement, and the ventilation rate of smoke exhaust fans, a comprehensive design solution can be established.

After activating the CCR system, the concentration of flammable gases can be effectively diluted, preventing it from reaching the explosive limit. This also corroborates the approach adopted in North American energy‑storage fire protection, which prioritizes explosion prevention as the primary measure and employs fire‑control and thermal‑spread mitigation as secondary strategies.




 Image 5 from Series Article Four.png

Therefore, the CCR system, as a critical safety system, must be capable of withstanding temperatures prevailing prior to a fire—specifically during thermal runaway—and must undergo testing under specified scenarios. Although the revised NFPA 855 does not explicitly require gas detector components to meet particular certification standards, the use of a certified gas detection system remains a prerequisite for initiating the CCR system (at concentrations ranging from 10% LFL to 25% LFL).