NFPA 2010, American Standard (2025 Edition): Guide for Calculating the Required Quantity of Aerosol Fire-Extinguishing Systems for Protected Spaces

Author:




Application of the U.S. Standard NFPA 2010 (2025)

Guideline for Calculating Aerosol Fire Extinguishing Agent Dosage and Number of Units




As energy‑storage containers and battery packs gain rapid traction in the Americas market, accurately calculating the required quantity of aerosol fire‑extinguishing systems in accordance with NFPA 2010 (2025 edition) has become a critical challenge in engineering design and commissioning.


This paper will begin with standard terminology to clarify the correct definition of “protected space,” thereby ensuring consistent communication throughout the design review, drawing approval, and handover phases, reducing computational discrepancies, and meeting regulatory requirements.



Q

When calculating the required quantity of aerosol fire suppression systems for a container or a PACK battery pack, is it necessary to deduct the volume occupied by the batteries and other combustible materials?



A

There is no need to deduct the volume occupied by the battery and other combustible materials.

According to Section 3.3.23, “Protected Volume,” of NFPA 2010 — Standard for Fixed Aerosol Fire-Extinguishing Systems (2025 Edition):

Volume enclosed by the building elements around the protected enclosure, minus the volume of any permanent impermeable building elements within the enclosure.

Its general meaning can be understood as follows: the protected space volume equals the total volume enclosed by the enclosure (protective) structure minus the volume of internal permanent impermeable components.




Q

In a real-world containerized battery storage facility, how are the required aerosol dosage and the number of necessary units calculated?


A


In NFPA 2010 – Standard for Fixed Aerosol Fire-Extinguishing Systems (2025 Edition), the definition of total aerosol charge is as follows:


The general meaning is:


Total aerosol dosage (g) = Design application density (g/m³) × Product of all additional design factors × Protected space volume (m³)


Our company has decomposed the design factor into a height compensation factor, K₁, and a leakage rate factor, K₂.


Accordingly, the formula for calculating our company’s total aerosol consumption is: m = dₐ × K₁ × K₂ × V


Calculation of the required number of aerosol fire extinguishers: N = m/mₐ


mₐ = the mass of the aerosol-generating agent for a single aerosol generator


K₂ depends on the ratio of the opening area of the protected space to its total surface area (including the floor), which is referred to as the leakage rate LR.





Next, let’s take a containerized battery compartment as an example:

A container S battery compartment / Dimensions (L × W × H): 5.2150 × 2.2690 × 2.5500 m


V=5.2150*2.2690*2.5500-0=30.1737m³-0=30.1737m³

The volume of permanent, non-permeable components shall be deducted: 0 m³ (assumed)


Select product model: QRR0.75G-U01

Design application density of the product for fire‑related scenarios: mixed‑fuel fires / 97.5 g/m³

The opening area of the protected space = 0.1 m² (assumed)

Surface area of the protected space = 61.83407 m²

LR=0.1m²/61.83407m²=0.1617%


The total aerosol dosage required for the protected space is m = 97.5 g/m³ × 1 × 1 × 30.1737 m³ = 2941.94 g.

Number of aerosol generators required for the protected space (QRR0.75G-U01): N = m/mₐ = 3.923 units (round up to 4 units)




From an interpretation of the American NFPA 2010 standard to specific calculation examples, we have thoroughly examined the definitions of relevant terms and the methods for determining the number and dosage of aerosol fire‑extinguishing systems in the Americas. Mastering these essential definitions and core calculation principles is a prerequisite for the successful design and implementation of projects. We hope this guide will serve as a practical tool in your work, providing robust support for the efficient and compliant development of fire‑protection systems.