NFPA 855 Water-Based Fire Suppression Systems: An Analysis (Part I) | AHJ Recommends “Not to Use Water Directly to Extinguish Fires in Battery Compartments”

Author:


Provisions of NFPA 855-2026 Regarding Water-Based Fire Suppression Systems

4.9* Fire Control and Extinguishment

Unless modified in Chapters 9 through 17, fire control and suppression shall be provided for rooms or areas within buildings containing ESSs.

4.9.3 Water Spray Fire Suppression System

Water spray fire suppression systems shall be installed in accordance with NFPA 13 or an equivalent standard.

4.9.3.1

For an ESS unit (or group) with a maximum energy storage capacity of 50 kWh, as specified in 9.5.1.1, the design density of its water spray fire‑extinguishing system shall be 0.3 gpm/ft² (12.2 mm/min), based on either the room area or a design area of 2,500 ft² (230 m²), whichever is smaller, unless a lower density has been approved pursuant to the fire and explosion testing requirements set forth in Section 9.2.

4.9.3.2*

The water spray fire suppression system for ESS units (groups) exceeding 50 kWh shall use a density determined in accordance with the provisions of Section 9.2, based on fire and explosion testing.

4.9.4 Automatic Fire Suppression Control and Extinguishing Systems

4.9.4.1*

Automatic fire detection and suppression systems shall comply with the following standards or their equivalents, unless otherwise modified in Chapters 9 through 17:

(1)NFPA 13

(2)NFPA 12

(3)NFPA 15

(4)NFPA 750

(5)NFPA 770

(6)NFPA 2001

(7)NFPA 2010

4.9.4.2*

Other automatic fire control and suppression systems shall be approved in accordance with the results of large-scale fire and explosion tests specified in Section 9.2.

4.9.5 Water Supply

4.9.5.1*

If required by other sections of this standard, the installation site for non-mechanical energy storage systems shall provide a permanent fire‑fighting water supply, unless otherwise specified in Chapters 9 through 13.

4.9.5.2

If permanent, adequate, and reliable fire‑fighting water supply is unavailable, the requirements of NFPA 1142 shall apply.

4.9.5.3

Where public or private water supply is available, readily accessible fire hydrants shall be provided for the installation of on-site energy storage systems.

4.9.5.4

Fire hydrants installed on private fire water mains shall be installed in accordance with NFPA 24.

0 1


Interpretation of the Standards
 

Compared with the 2023 edition, NFPA 855‑2026 expands the scope of permitted automatic fire suppression systems for energy storage systems.

Compared with the previous edition of NFPA 855, this standard places various fire suppression systems—such as those specified in NFPA 13, 15, 750, 770, 2001, and 2010—on an equal footing for compliance, no longer referring to them as “alternative approaches.”

System selection and acceptance are guided primarily by standardized test evidence, and with… According to Section of NFPA 855-2026 The output-phase logic correlation of UL 9540A and large-scale fire tests as required by Section 9.2;

At present, other automatic fire suppression systems can directly replace water-based fire suppression systems and are not required to undergo testing as mandated by the previous edition of Standard 855. The automatic fire suppression system selected for energy storage systems must comply with the relevant NFPA codes, and if multiple suppression systems are installed, they must be designed to ensure that they do not interfere with one another.

02


Problems with the water fire suppression system


 

1

Water can only provide physical cooling and cannot effectively extinguish a fire.

2

For energy storage power stations, not all facilities can meet the water supply requirements stipulated by NFPA or other regulations.

3

Fire‑fighting water, after use, contains soluble metal ions and must therefore be fully recovered to meet environmental regulations. To this end, energy‑storage stations are required to be equipped with collection and storage systems that comply with these requirements.

4

Under extreme conditions such as explosions, water fire sprinklers may fail under the impact of the force, thereby reducing their temperature-control effectiveness.

5

Conventional water‑based fire‑protection systems used for energy storage, such as dry‑pipe manual‑actuation systems, are not classified as automatic sprinkler systems and therefore fall outside the scope of NFPA 855‑2026; consequently, their use must be validated through testing.


03


Development Trends of Water-Based Fire Suppression for Energy Storage Systems



In terms of standardized design logic, NFPA 855 does not impose a blanket prohibition on water‑based systems; rather, it specifies the scenarios in which such systems must be installed. For unattended areas or container‑level standalone systems, sprinkler systems may be omitted. Water‑based systems are primarily intended to cool adjacent containers that have not yet ignited and to control thermal spread, rather than to directly extinguish burning battery cells. If a water‑based system is incorporated into the design, the piping network may be routed externally to the container. The system should include wastewater collection and separation facilities to prevent the discharge of electrolyte‑containing or heavy‑metal‑contaminated effluent.

TODD.JPG

In the AHJ’s view, the current code contains no explicit provision stating that “eliminating the water system is safer.” The AHJ maintains that sprinkler flow rates are difficult to control and cannot be fully contained; if improperly managed, they may instead introduce new environmental and electrical hazards. A reasonable approach is to use aerosols, gases, or… in unoccupied areas or enclosed enclosures. TRPP System Protection ; If a water-based system is used, it should be limited to external cooling applications. The AHJ recommends against using water directly to extinguish fires in battery compartments. , because the required water volume is substantial and it is difficult to achieve complete collection and treatment of wastewater. If water use is unavoidable, it should be employed to cool adjacent unburned containers, thereby preventing thermal spread; moreover, a collection and separation system must be installed for the resulting wastewater to prevent the discharge of electrolyte‑containing or heavy‑metal‑contaminated effluent.

Therefore, incorporating water-based fire suppression systems into energy storage containers does not significantly enhance their fire safety; on the contrary, the associated drawbacks may give rise to other related issues. Accordingly, gradually replacing in‑cabin water‑based fire‑suppression systems with other high‑efficiency fire‑extinguishing systems is a future trend in fire‑protection design.