“Energy Storage Fire Protection: Global Regulatory Updates” – Germany Edition: Containing Spread Is the Bottom Line; Aerosol Systems Are the Recommended Fire Suppression Solution

Author:


01

Introduction

As the global installed capacity of energy storage systems rapidly expands, fire safety in energy storage has become a core issue that constrains the industry’s healthy development. Countries have successively updated relevant technical standards and fire‑safety guidelines, and regulatory approaches are gradually… Shifting from “post‑incident firefighting” to “prevention plus early suppression” Regulatory requirements in the energy storage fire‑protection sector vary in emphasis, yet a common trend is becoming increasingly evident: automatic fire‑extinguishing systems have become an essential component of energy‑storage projects. Among the many fire‑suppression technologies, aerosol agents—owing to their highly effective suppression of lithium‑battery fires and their strong adaptability to diverse application scenarios—are being recommended in an ever-growing number of technical standards.

This series of posts will focus on analyzing the technical preferences of various countries regarding the selection of fire suppression systems, providing compliance guidance for energy storage system integrators, owners, and design firms. This installment primarily centers on… Germany’s “Preventive and Extinguishing Fire Safety Recommendations for Large-Scale Lithium-Ion Energy Storage Systems” This paper elaborates on the key requirements for the design of energy storage fire protection systems.


02

Background

Germany’s newly updated “Preventive and Extinguishing Fire‑Protection Recommendations for Large‑Scale Lithium‑Ion Energy Storage Systems” deserves close attention from the industry. The document was jointly issued by the German Professional Fire Service and the German Fire Protection Association, and was developed in coordination with organizations such as BVES, GDV, and VdS. It represents a consensus among stakeholders in the fire protection, insurance, and energy storage industries.

The document explicitly states that energy storage systems are classified as special-purpose structures subject to no specific regulations, and must undergo assessment by a fire safety expert or consultant and pass a fire‑technical review before they can be implemented. This indicates that, The design must give priority to fire safety measures, including fire prevention, fire suppression, and ventilation, and undergo rigorous technical review and approval.


03

On-site Compliance Analysis

Currently, U.S. standards such as UL 9540, UL 9540A, and NFPA 855 are being used to address gaps in existing European standards, particularly in the areas of fire and explosion protection. While these U.S. standards can serve as a temporary supplementary solution to avoid redundant testing, even full compliance with them still poses challenges for European applications, primarily due to repeated testing requirements and complex citation chains.

As With the gradual refinement of European standards, such as EN IEC 62619, U.S. standards will primarily serve as interim references. By appropriately integrating existing EN standards, many technical gaps have now been effectively addressed. In addition, new IEC and EN standards are currently under development and will align with the requirements of the EU Battery Regulation (BattVO), particularly by introducing more stringent provisions on fire safety and explosion protection.


04

Fixed Fire Protection System Design
4.1

Automatic fire suppression systems have become a mandatory requirement.

In the “Preventive and Extinguishing Fire Safety Recommendations for Large-Scale Lithium-Ion Energy Storage Systems” It is pointed out that large-scale battery energy storage systems typically operate autonomously with no personnel present under normal conditions, and human access is permitted only during maintenance. In the event of a fire, for safety reasons, personnel can approach only to a limited extent, and the fire may still spread rapidly. Furthermore, in locations where a potential fire involving a battery energy storage system could pose a threat to personnel or the environment, as well as where property protection is required, Automatic fire alarm and suppression systems must be installed. Such devices should be capable of promptly detecting and extinguishing incipient fires, controlling the spread of flames, and thereby preventing further fire propagation.






























































































4.2

Tiered Protection: Allows for single-point failure while preventing thermal runaway.

Similar to the TRPP system proposed in NFPA 855‑2026, this document also suggests designing module‑level fire suppression systems to mitigate fires caused by early thermal runaway and to prevent thermal… Spread 。 This indicates that the system permits the failure of the first faulty cell, but must prevent thermal runaway from propagating further to adjacent cells, modules, clusters, or the entire compartment.

This requirement has directly spurred the adoption of Pack‑level fire suppression systems, thereby realizing the design philosophy of “precise protection and early containment.”





























































































4.3

Fire-extinguishing agent selection: Aerosol is rated as “suitable,” while FK‑5‑1‑12 is not recommended.

In selecting a fire suppression system, the performance of mainstream extinguishing agents was compared through experimentation. As shown in the table:

· FK-5-1-12 It is not entirely suitable as a fire‑extinguishing agent for lithium‑ion fires, and the accompanying notes explicitly state that FK‑5‑1‑12 cannot prevent thermal runaway; therefore, It should not be used as the primary means of extinguishing this specific hazard. 。

· In contrast, Aerosol In all applicable protected areas, including open‑type battery rooms, enclosed battery cabinets, electrical control rooms, and cable trays, the rating is “suitable,” indicating that… It offers improved scenario adaptability for both the battery cells themselves and the surrounding space within energy storage systems.





























































































4.4

Explosion-proof ventilation system

During the early stages of thermal runaway, lithium-ion battery energy storage systems release large quantities of flammable gases, creating a risk of flammable gas‑air mixture accumulation within the enclosure. If ignited at this stage, deflagration or explosion may occur. Accordingly, this document explicitly mandates that… It is necessary to design an explosion‑proof ventilation system comprising a fan and an explosion‑relief panel, and to integrate it with other systems to jointly ensure explosion‑proof safety.


05

Conclusion

0 1

U.S. standards can serve as a reference, but they should not be copied outright.

UL 9540A, NFPA 855, and similar standards are better suited to address current gaps in Europe regarding thermal runaway propagation assessment and installation‑related risk mitigation. The project should ultimately still be based in Europe. Primarily based on EN/IEC standards and the local fire safety and building codes of various countries.

0 2

In-cabin fire suppression System Further tiered allocation is also required.

Pack‑level aerosols can be used for localized fire‑spread prevention, while compartment‑level aerosols are suitable for the rapid suppression of incipient fires within battery compartments.

0 3

Aerosol is a recommended fire suppression system.

Through experimental comparisons, aerosols were rated as… in multiple typical energy storage scenarios. “Suitable.” The pack‑level and compartment‑level aerosol fire suppression system, in conjunction with an explosion‑proof ventilation system comprising fans, gas detectors, and venting panels, fully complies with the principles of tiered protection, early containment, and prevention of spread as emphasized in the report.