14
2025
-
11
A Comprehensive Guide to Overseas Energy Storage Compliance (Part 3): AHJ Experts Address the High-Level Concerns Raised at a Closed-Door Meeting in Europe
Author:
At a closed-door session of the Overseas Energy Storage Fire Safety Forum, we engaged in dialogue with industry experts and subsequently compiled a summary of real‑world, on‑the‑ground Q&A. In the first two installments, we focused on the North American and Australian markets; in this final installment, we turn our attention to Europe. As the European energy storage market expands rapidly, is NFPA 855 applicable there? Are large‑scale fire tests mandatory? Can water‑based fire suppression systems be eliminated? This article provides answers to these questions, offering a comprehensive guide to the key compliance requirements and acceptance strategies for energy storage fire safety in Europe.
1. Does the TRPP system mentioned in NFPA 855 2026 apply to Europe?
In Europe, referencing NFPA 855 is an option, and similar standards are expected to be introduced in the future. At present, the acceptance process involves a significant degree of subjectivity on the part of the Authority Having Jurisdiction (AHJ). While TRPPs are not yet mandatory in Europe, their use is being encouraged, which should make it easier for AHJs to approve installations during inspections.
2. Is large-scale fire testing mandatory in Europe?
In Europe, there are currently no mandatory regulations; the prevailing reference is NFPA 855. Providing a large‑scale fire‑test report can facilitate smoother approval during the acceptance process.
3. Does the fire protection system require a dedicated UPS?
An independent UPS is not necessarily required; a shared UPS or a generator may be used, provided that the required backup duration can be ensured. Two conventional power feeds can serve as mutual backups, on the condition that the power‑transfer switching is reliable and that the system meets the regulatory requirements for continuous operation during a power outage.
4. In Europe, when calculating the aerosol volume inside an energy storage container, can the volume of the battery pack be subtracted?
Cancellation is not permitted, as EN 15276‑2 specifies: the volume enclosed by architectural elements surrounding a protected enclosure, minus the volume of any permanent, impermeable architectural elements within that enclosure. We consider the battery pack to be an item that can be removed at any time and may also be incinerated; therefore, it cannot be deducted.
5. Is the fan’s backup power required to be supplied from the container or the terminal?
Backup power only needs to meet certification and compliance requirements; it can be provided by a container or a terminal, but it must ensure an independent and sufficient power supply.
6. Can the water-based fire protection system be eliminated?
At the power‑station level, the water system can be omitted within the container, and an onboard water system may pose challenges for recycling.
7. How should water pollution caused by water-based firefighting be addressed after a fire?
Europe places a strong emphasis on environmental protection, requiring the construction of sewage collection pits around container terminals and the use of pumps to remove wastewater, thereby ensuring that local ecosystems remain unaffected.
8. According to European standards, what requirements must European‑standard fire‑resistant cables meet? What are the requirements for using conduit or cable trays?
There is no mandatory requirement for protective measures, but the cable must meet its own flame-retardant and fire-resistant ratings. The minimum fire resistance is 30 minutes (the cable must not burn through and must maintain normal functionality).
9. Can a thermal‑start device be used for fire suppression inside an energy‑storage container/cabinet?
EN 15276‑2 stipulates that heat‑activated automatic devices shall not be used in areas that are normally unoccupied, and energy‑storage containers/cabinets are considered to be such unoccupied areas.
10. Is perfluorohexanone subject to usage restrictions?
From an environmental standpoint, the thermal decomposition and hydrolysis of perfluorohexanone generate harmful substances such as hydrogen fluoride (HF). Europe is systematically phasing it out, and perfluorohexanone also suffers from reliability issues like leakage, while its cost remains very high; therefore, its use is not recommended.
Related News