A Comprehensive Guide to Overseas Energy Storage Standards Compliance (Part 1): AHJ Experts Address the High-Level Concerns Raised at the North American Closed-Door Meeting
Author:
Answers to questions from the North American closed-door meeting: leading experts address current hot-button issues.

1. Why does the owner require a NFPA 855 compliance report?
This is understandable. The NFPA 855 requirements already incorporate HMA analysis, which can be regarded as a project‑level risk control checklist. Therefore, providing an NFPA 855 compliance report helps clients assess the system’s overall safety and regulatory compliance.
2. What are the core safety objectives and future development directions of the new edition of NFPA 855?
AHJ summary: The core requirements of the new edition of NFPA 855 can be summarized into three protective objectives:
① Early detection; ② Prevention of spread; ③ Prevention of personal injury
Regarding future development trends, AHJ believes that BESS is an emerging technology that is inherently safe, and the perception of frequent accidents largely stems from excessive media coverage. Compared with conventional oil- and gas‑based facilities, the thermal runaway risk of BESS is more manageable, and with the refinement of standards and ongoing design improvements, its safety will continue to improve.
3. Does Tesla’s energy storage solution comply with NFPA 855 requirements? In which regions can it be deployed?
The AHJ has explicitly stated that Tesla’s energy‑storage fire‑protection approach as a whole does not comply with NFPA 855 and will not be directly accepted in most states, particularly those with stringent enforcement. If a project adopts a similar solution, it must submit to the AHJ comprehensive technical documentation, risk analyses, and third‑party test reports—such as UL 9540A, CFD simulations, and explosion‑proof testing—to demonstrate its safety. This approach is not inherently prohibited; rather, approval requires thorough justification and compliance substantiation. Currently, Tesla has incorporated additional detectors into its latest containerized systems to meet regulatory requirements. With the exception of Los Angeles County, most jurisdictions will permit such installations upon adequate justification.

4. What is the relationship of applicability between NFPA 68 and NFPA 69, and what are the compliance pathways?
NFPA 69 serves as the primary explosion‑proof standard, while NFPA 68 provides a supplementary verification method. The system should prioritize compliance with NFPA 69 to ensure that the explosion‑protection objectives are met (average concentration ≤ 25% LFL, peak concentration ≤ 60%). If it is not possible to fully satisfy NFPA 69’s requirements for controlling the average concentration of flammable gases, a partial‑volume deflagration analysis may be conducted, and a NFPA 68 venting test or CFD simulation can be performed to validate the behavior of that specific gas volume. If simulations or field measurements demonstrate that the container enclosure can withstand a localized deflagration, a venting panel is not required. However, if the average flammable‑gas concentration within the space falls between 25% and 60% LFL, failure to install a venting panel necessitates additional explosion‑testing evidence to confirm safety.
5. What is the priority between explosion protection and fire suppression?
Explosion protection takes priority. Even when aerosol or water‑based systems are employed, explosion safety must be ensured first. The TRPP system is the most effective means of early intervention to mitigate thermal runaway and minimize losses.
6. Is TRPP a mandatory requirement? Who is responsible for its implementation?
TRPP is not mandatory but strongly recommended and constitutes a plus for HMA. It should be centrally controlled by the fire alarm control panel; the BMS may interface via relays, but it must not directly drive the device. The JAD thermal‑start scheme requires scheduled testing and validation. In the absence of a dedicated UL standard at this time, the scheme’s safety can be verified through witnessed testing.

7. Can large-scale fire tests be exempted due to spacing requirements?
No. All systems must undergo a large‑scale fire‑test, and even with a spacing of ≥0.9 m, no exemption applies. During the test, the unit under evaluation shall not be equipped with a fire‑suppression system; if the surrounding units’ fire‑suppression systems do not activate, the test is considered successful.
8. Is a fire suppression system required for large-scale burn tests? How is the success of the test determined?
During large-scale fire‑testing, the container under test is not equipped with any fire‑suppression system to assess the extent of natural flame spread. If, during the test, no thermal runaway occurs in the batteries of adjacent containers, the test is deemed successful, demonstrating that the fire has not propagated.
9. What are the requirements for UPS backup runtime under the new edition of NFPA 855?
The backup power for the alarm and fire‑extinguishing systems must ensure 24 hours of standby plus 2 hours of operation. The CCR system requires HMA analysis and validation. The UPS may be shared or supplemented by a generator, provided that the required duration is guaranteed.
10. Is a water-based fire suppression system required in energy storage systems? If a water-based system is not used, is this compliant with regulations?
The AHJ stated that the design rationale of NFPA 855 does not impose a blanket prohibition on water‑based systems, but rather specifies the circumstances under which such systems must be installed. In unattended areas or for container‑level standalone systems, sprinkler systems may be omitted. Water‑based systems are primarily intended to cool adjacent containers that have not yet ignited and to control thermal spread, rather than to directly extinguish burning battery cells. If a water‑based system is incorporated into the design, the piping network may be routed externally to the container. The system should include facilities for collecting and separating wastewater to prevent the discharge of pollutants containing electrolytes or heavy metals.

11. Is there evidence to suggest that eliminating the water system is safer?
Currently, the standard library does not contain an explicit provision stating that “water‑based suppression systems are safer.” The AHJ’s position is that the amount of water discharged by sprinkler systems is difficult to control and cannot be fully contained; if used improperly, such systems may introduce new environmental and electrical hazards. Protective measures should be implemented in unoccupied areas or within enclosed enclosures, with aerosol, gaseous, or TRPP systems being appropriate options. If a water‑based system is selected, its application should be limited to external cooling only.
12. How should wastewater be handled after a fire?
The AHJ recommends avoiding the direct use of water to extinguish burning battery compartments, as this requires substantial quantities of water and makes it difficult to ensure complete collection and treatment of the resulting wastewater. If water must be used, it should only be applied to cool adjacent, unburned containers to prevent thermal spread; a collection and separation system should be installed to prevent the discharge of effluents containing electrolytes or heavy metals.