17

2025

-

10

In-Depth Analysis and Compliance Guide to the 2026 Edition of NFPA 855 (Part 3) — Detailed Explanation of Large-Scale Fire Test Requirements

Author:


The online version of NFPA 855 (2026), published on the NFPA website, relocates the fire and explosion testing requirements from Section 9.1.5 to Section 9.2, while tightening the requirements for test procedures. This change marks a new phase in the safety assessment of ESS (energy storage systems).

Original text of version 9.1.5, 2023

In In the 2023 edition, the relevant requirements state:

“When required by other sections of this standard, representative energy storage systems (ESS) shall be subjected to fire and explosion testing in accordance with the provisions of 9.1.5, and such testing shall comply with UL 9540A or an equivalent test standard.”

Original text of version 9.2, 2026

And the requirement in the 2026 edition is:

“When required by other sections of this standard, representative energy storage systems (ESS) shall be subjected to fire testing in accordance with Section 9.2, which shall comply with UL 9540A and include large-scale fire testing, to collect the following data: gas release characteristics at the cell level, thermal runaway propagation potential at the module level, and thermal runaway propagation potential between energy storage systems.”

Previously, the requirements primarily applied only to UL 9540A; however, in the 2026 edition, the requirements have been expanded to include large-scale fire testing under UL 9540A.

Meanwhile, in the 2026 edition, section 9.2.1.2 introduces new test requirements for “active ignition”:

“When thermal runaway of a battery cell results in the release of flammable gases during cell‑ or module‑level testing, additional tests shall be conducted at the system unit level to intentionally ignite these released gases, thereby assessing the risk of fire propagation.”

The UL 9540A test procedure induces thermal runaway at the cell, module, system‑level, and installation levels, and collects the resulting data to assess fire and explosion hazards.

However, under the current version of UL 9540A, if a product passes testing at one level, the evaluation may conclude at that level without proceeding to the next. Many stakeholders argue that limiting testing to the unit level fails to capture the ESS’s performance under more severe fault scenarios, and thus such testing cannot truly be considered “large‑scale.”

The 2026 revised standard mandates that ESSs must undergo both UL 9540A testing and large‑scale fire testing. Under this provision, the large‑scale fire test will, like the current UL 9540A, serve as a threshold requirement for market access.

Original text of G.11.6, 2026 edition

Additionally, in the appendix In G, Chapter 11 has been expanded to include the “Guidance for Conducting Large-Scale Fire Tests (LSFT).” This section also provides relevant guidance on venting panels and “door-opening tests,” topics of particular concern to many BESS manufacturers.

1. The explosion venting area designed in accordance with NFPA 68 shall be opened at the commencement of testing, while openings in non-deflagration venting areas shall remain closed.

2. If there is no explosion venting design, or if the design does not comply with NFPA 68 requirements, doors and other openings that are not normally open during normal operation shall be opened prior to the start of testing and kept open throughout the entire test—this is known as an “open-door test.”

3. The NFPA 69 system is not considered; it shall be assumed that it does not suppress the ignition of gases released during thermal runaway of one or more battery cells, meaning that the ventilation fans shall remain off.

Currently, Ji’andun is collaborating closely with AHJ, a leading North American authority, as well as other renowned industry‑wide testing organizations. Together, they have established a large‑scale fire‑exposure test laboratory that meets relevant standards, with testing capabilities recognized by international bodies such as UL. The company offers clients specialized consulting on large‑scale fire‑exposure testing, assistance in developing tailored test protocols, and support in securing qualified personnel and facilities—helping customers confidently navigate new regulatory requirements and achieve safety compliance.